Saturday, May27, 2017 L-36.com

' Raritan Phii Toilet'




NOTE: DO NOT HIT REFRESH!!! These files are big and can take a long time to load. This file is 0.16 MB. Give it time.
If there is text in the file, you can scroll it while the image loads. Enjoy

View PDF

Image Preview



Ad by Google

PDF to Text

PHII AND PHEII MARINE TOILETS
INSTALLATION AND MAINTENANCE INSTRUCTIONS
THE FOLLOWING ARE CAUTIONARY STATEMENTS THAT MUST BE READ AND FOLLOWED
DURING BOTH INSTALLATION AND OPERATION
WARNING Raritan Engineering Company Inc recommends that a qualified person or electrician in the case
of PHEII install this product Equipment damage injury to personnel or death could result from
improper installation Raritan Engineering Company Inc accepts no or liability for
damage to equipment or injury or death to personnel that may result from improper installation or
operation of this product
WARNING Hazard of Flooding Any installation made below the waterline must have vented loops positioned
properly and all hose connections should be Both intake and discharge seacocks
should always be in the closed position when the toilet is not in use Failure to do so may result in
flooding property damage and loss of life
WARNING Hazard of Fire Do not wire 120V PHEII motors without using specified rectifier
Do not operate PHEII series toilets with handle in place serious bodily injury may occur
INTRODUCTION It is advisable to flush the toilet briefly before use to
The PHII is a manual marine toilet The PHEII has minimize staining Pumping several strokes after the
either electric push button or manual operation Both bowl has been flushed will help to clear the have the same overall dimensions An electric
minimize odor and reduce the possibility of PHECKII that mounts between the bowl and into the bowl It may be necessary to change the
pump converts a PHII to a PHEII with no additional valve handle from FLUSH to DRY more than
floor space required once to properly evacuate the bowl
Valve handle must be fully in the FLUSH or
The PHII and PHEII are available with a
DRY position bowl and seat or with bowl and seat Hard objects or stringy substances paper towels
feminine hygiene products filter cigarettes etc
Space requirements for each are as follows
must not be thrown into the toilet as they will cause
Models Height Depth Width damage
bowl 12 14 21 18 14
RETURNING PHEII TO MANUAL OPERATION
Marinesize bowl 11 78 21 17 34
All models are suitable for use in conjunction with WARNING Secure circuit breaker in LectraSan MC a Coast Guard Certified position
before I flowthru Marine Sanitation Device MSD In the event of a power loss or problem with the
andor holding tanks electrical system
OPERATION 1 Remove arm bolt and nut 1115 and 1115A
from the connecting rod DO NOT adjust valve while toilet is operating bodily injury 2 Displace connecting rod 1116BW from track
may occur and push toward the back
The intake valve handle 1209BW must be in the 3 Insert the handle 1206W and cotter pin
open or FLUSH position to 1210A Be sure the handle is completely in the
draw water in When the valve handle is in the handle socket and secured by the cotter pin to
DRY position a special air valve allows the toilet to avoid the possibility of breaking the plastic sock
be pumped dry without pressure build up In the et position toilet will only pump out no water To return to electrical operation reverse be
brought into the bowl
MAINTENANCE instructions for ratio Place
Using CP a bioenzymatic toilet bowl cleaner intake hose in this bucket Place discharge from Raritan Engineering will keep the
into the empty bucket Pump toilet until clean and fresh smelling Introducing Raritan has circulated and is being
into flush water through a Toilet Water 4 Antifreeze should remain in the toilet until
Kit TWK will deodorize and lubricate the unit This will protect both intake
Super Lube SL applied to the piston rod will and discharge sides of the pump the life of the Piston Shaft Seal This should antifreeze into the
bowl will only protect the
be done every spring and fall or more regularly if the discharge side of the pump allowing the intake
head is used frequently side to possibly Using improper deodorants or NOTE Holding tanks
seacocks and can result in damage to rubber and systems need to be independently parts DO NOT USE pine oil
stored and see ammonia ethyl acetate phosphoric and concentrated chlorine bleach petroleum
solvent based products
1 Lubricate piston rod with Super Lube
PHEII units should have Super Lube applied to the
2 Using the buckets hoses and a gallon 38 rod 1116B slot where the roller
of clean water flush the antifreeze out of and to the track on the side of the pump
toilet Dispose of antifreeze properly in
housing where the connecting rod travels up and
accordance with local and federal 3 Reconnect the hoses and open both attempting repairs refer to
section of this manual 4 Check all connections for leaks with several test
flushes
STORAGE
Short Term Storage INSTALLATION OF REPLACEMENT PARTS
If the toilet is not going to be used for up to one week 1 Refer to Fig 2 when replacing part the toilet several strokes with the shutoff handle 2 If
Valve Body 1203BW is removed it must be
in the wet bowl position to clear all lines positioned as in Fig 3 for proper Term Storage
Overhaul kits containing the parts normally required
If the toilet is not going to be used for over a week to repair each unit are available In addition the short term storage then switch to the dry
parts for your toilet may be ordered through your
bowl position and purge the toilet with at least two dealer or direct from the of fresh water added to the bowl
INSTALLATION
WINTERIZING To install PHII and PHEII marine toilets winter lay up is a major cause of marine installation
accessories are failures 1 A nominal 34 19mm thruhull fitting and
1 Close the intake and discharge seacock Disconnect seacock shutoff valve
and drain the intake and discharge hoses 2 34 19mm ID reinforced intake hose and
Winterize seacocks and hoses stainless steel hose clamps
2 You will need two buckets three feet 9M of 3 1 12 38mm ID reinforced sanitation discharge
34 19mm hose three feet 9M of 1 12 hose Raritan SH and stainless steel hose
38mm hose and a quart 95 liter of nontoxic clamps
antifreeze
4 A nominal 1 12 38mm discharge thruhull
3 Prepare one half gallon 19 liters of an antifreeze fitting with seacock may be required depending
water mixture in a bucket refer to the antifreeze on the specific 2
Super Lube is a registered trademark of Synco Chemical Corp
5 PHEII units require wire terminal ends a 1 Route discharge hose above discharge outlet
momentary switch and a relay PBS and CDS with a vented loop This will enable the toilet to
6 PHEII units that will be operated on 120 VAC discharge more efficiently and will help to prevent
shore or generator power require a full wave backflow
bridge rectifier in the circuit Raritan CH104 is 2 A InLine Strainer 163000 is recommended
a combination rectifier and activating switch This will help minimize odors and help prevent
MOUNTING and PHEII may be mounted above or below the 3 Intake and discharge
thruhull fittings should be
waterline Figs 1 and 1A Vented loops VL34 located far enough apart and in such a manner as
and VL1 12 are required for below waterline to prevent discharge water from being and hose connections must be double
through the intake One means of Mount unit securely on a flat solid deck this is to place them on
opposite sides of the hull
using stainless steel bolts backed up with nuts and Intake thruhull should be located so that during
large washers or stainless steel lag screws long enough shallow water conditions sand and other debris
not to pull out Never mount PHEII where it may are not drawn into thruhull fitting
be subject to shower spray or other sources of 4 The optional Raritan Toilet Water Kit water
permits use of Raritan Concentrate CON22
PLUMBING with the PHII and PHEII toilets Below waterline installations require
Concentrate deodorizes the bowl and loops Top of the loop must be above internal at greatest angle of heel Intake
vented 5 Test flush and check for leaks
loops must be installed between pump and back of
the bowl Discharge vented loops must be the discharge of toilet and seacock See
Fig 1 and 1A
FIG 1 ABOVE WATERLINE INSTALLATION
Vent Fig 2
PHII Marine Outside
Vented Hull or Deck Toilet
Toilet WRONG
Loop Base
Correct Orientation of
Waterline Waterline 1228CW Flapper Valves
InLine LectraSan MC
Strainer
Intake ThruHull Discharge
and Seacock Drawing Not To Scale ThruHull and Toilet
Seacock CORRECT
Base
Fig 3 NOTE Before Rein
FIG 1A BELOW WATERLINE INSTALLATION Deck Pumpout
stalling 1209BW Valve
Handle Be Sure Points
InLine
A and B On The
Strainer Vented
Vented Vented Loop Loop Inlet Valve Body
Loop 1203BW Are Posi
Y Valve tioned As Shown By
The Double Arrow
Waterline Waterline
Holding Tank POINT A
Intake Discharge
ThruHull ThruHull
and Seacock and Seacock
PHII Marine POINT B
Toilet
LectraSan MC
Drawing Not To Scale
ELECTRIC CONVERSION KIT INSTALLA WIRING THE PHEII
TION PHECKII For PHII Models Only WARNING DO NOT wire a 120V PHEII motor
NOTE It is recommended that the toilet be directly to 120VAC service unless a rectifier has
removed before installing the PHECKII been added to the circuit motor burnout short
1 Close the seacocks circuiting and fire could result
2 Remove cotter pin 1210A and handle Refer to Fig 5 to determine correct wire and circuit
1206W from toilet Disconnect hoses and breaker sizes Locate fuses and circuit breakers for
unbolt toilet from deck easy accessibility and on a circuit separate from other
accessories 12 24 and 32 VDC units require a
3 Align connecting rod in track on side of pump momentary switch and a heavy duty relay rated for
housing and place motorgearbox unit in position continuous service See Fig 4 for wiring diagram
on base 1248W between pump and bowl The momentary Push Button Switch PBS and
4 Insert four hex head screws 1119A with lock Continuous Duty Solenoid CDS are available
washers 1118 Tighten evenly through Raritan
5 Insert bolt 1115 through connecting rod All PHEII120 models and PHECKII120 conversion
1116B and thread into yoke 1211PL kits are supplied for DC operation 120V DC units
Tighten jam nut 1115A securely this require a doublepole momentary switch rated for 10
connection is not a pivot point amps inductive load CHDPS120 For AC operation
a fullwave bridge rectifier is required CH104
includes rectifier and one double pole 14 363cm
WALL WALL
14 DECK DECK 4 12
18 14 465cm 114cm
17 34 454cm 22 14 566 cm 19 12495cm
20 508 cm 17 432cm
WALL AT REAR OF TOILET
9 14 DISCHARGE 5 14
236cm HOSE HOLE 134cm
Raritan PH IIPHE II
254cm 4
102cm
Marine Toilet with
Marinesize Bowl
LONGITUDINAL
229cm Front View Side View
127cm CENTERLINE
3 12
OF TOILET
and Footprint
89cm 102cm
Dimensions are for a Bowl
INLET Marinesize Bowl Dimensions in Parentheses
HOSE HOLE
Fig 4 Wiring the PHEII DC Unit with Momentary Electrical
Pushbutton Switch Nominal Voltage Volts DC 12V 24V 32V
Pushbutton Switch
PBS 3 Amp Fuse or Amperage Draw Nominal Voltage 18 11 8
Circuit Breaker Circuit BreakerFuse Size Amps 25 20 12
14 Awg
Wire Main Fuse or Circuit Breaker For 120vdc units use 14 AWG 25mm2 wire
See Specification Chart
Wire Sizes
Pos Voltage from
NOTE Recommended conductor sizes based on 105C rated
Battery or DC Power
Panel insulation Refer to ABYC Standards for other insulation ratings
Solenoid Relay Battery
CDS Lug Distance from source to unit and back to source feet m
UNITS 1031 1546 2061 2572 3092 40122 50152
POS Orange Motor Wire VOLTAGE Minimum recommended conductor wire AWG mm2
PHEII Motor for 3 voltage drop
12 1060 1060 8100 6160 6160 6160 4250
NEG Black Motor Wire 24 1615 1425 1240 1240 1060 1060 8100
Ground 32 1810 1615 1615 1425 1425 1240 1240
PROBLEM POSSIBLE CAUSE CORRECTION
A Electric motor labors pumps A1 Low Voltage at motor while running A1 Check condition of batteries terminals and wire con
slowly or handle is hard to nections for corrosion Check gauge of wire to be sure
pump on manual toilet it is not undersized
A2 Air pocket in discharge line A2 Clean vent fittings
A3 Holding Tank vent clogged or tank A3 Clean holding tank vent or empty tank as needed
full
A4 Discharge line obstructed A4 Check thruhull fitting for clog Remove discharge
hose if necessary to free obstruction
A5 MSD clogged A5 See MSD instruction manual
A6 Discharge seacock closed A6 Open discharge seacock
B Leak around piston shaft B1 Cartridge seal worn B1 Replace piston shaft seal cartridge assembly
B2 Piston shaft scored B2 Replace pistonrod assembly
C Water accumulates in the bowl C1 Flapper valve not seated properly C1 Close intake valve and pump dry Clean or replace
too fast flapper valve
C2 Joker Valve not closing or opening C2 Close intake valve and pump dry Clean or replace
properly joker valve NOTE Routing discharge hose above
toilet helps joker valve close tighter
C3 Calcium buildup or blockage in hoses C3 Clean affected parts or replace hose
and fittings
C4 Air pocket in discharge line C4 Bleed or clean vent fitting of vented loop or holding
tank vent
D Water rises in bowl at dockside D1 Joker Valve leaking D1 Close discharge seacock then intake seacock to deter
toilet below waterline mine which is causing the problem Clean or replace
joker valve A vented loop is needed in the discharge
D2 Intake Valve leaking D2 Check for debris lodged under check ball
Replace Orings check ball and spring if needed
D3 Too much pressure against check ball D3 Vented loop must be installed between the bowl and
pump Fig 1A
E Odor comes from head area E1 Marine vegetation lodged in bowl E1 Remove bowl and pressure flush from spud fitting at
when flushed the back of the bowl NOTE Installing a InLine
Strainer 163000 in the intake line will help prevent
recurrence
E2 Intake water is foul E2 Raritan Toilet Water Kit TWK and Raritan Concen
trate CON22 will aid in deodorizing intake water
E3 Back pressure from holding tank E3 Tank full or vent clogged Discharge line blocked or
kinked Clean or replace as necessary
E4 Contaminated discharge hose E4 Replace with Raritan Sanitation Hose SH
F Not enough water to rinse bowl F1 Intake valve positioned improperly F1 See Fig 3
F2 Bowl rinse holes clogged F2 Clean as needed
F3 Intake line or strainer clogged F3 Clean line or strainer
F4 Debris around intake or discharge valve F4 Remove check balls and clean
ball
F5 Scored pump housing or worn piston F5 Replace housing or O ring as necessary
Oring
F6 Worn housing or seal cartridge is F6 Replace housing or cartridge
drawing air
Units requiring extensive repairs may be returned to the Millville NJ or Fort Lauderdale FL office for overhaul Instructions address and phone number
MUST accompany returned units 5 to ensure proper handling
PARTS FOR RARITAN PHII AND PHEII Part No Description
MARINE TOILET 1106W Coupling wSleeve complete
Part No Description 1108A Motor Mounting Nut 2
1115 3816 x 1 12 Hex Head SS Bolt2 1109 Motor 12 24 32 120V DC
1124 14 20 x 12 RH Machine Screw 1110 O Ring
1200CW Pump Housing 1112 Link
1201 Intake and Discharge Valve Ball 2 1113 Link Pin Worm Gear Pin
1202 Intake and Discharge Valve Gasket 2 1115 38 16 x 1 12 Hex Head SS Bolt
1203BW Intake Valve Body wO Rings 1203B 1115A 38 16 Hex Jam Nut SS
1203B1 1203B2 1203B3 1116BW Connecting Rod Assy 1116B 1114B
1203W Air Valve Assembly 1114D
1204B Intake Valve Cap 1117B Crank Bolt
1206W Handle 1118 Lock Washer 4
1209BW Valve Handle 11191119A Hex Head Screw 4
1210 Handle Socket 1120W Worm Gear Assy1111 1113 1120
1210A Cotter Pin 4 1122 O Ring
1211PL Piston Rod Yoke 1123 Gear Box Cover
1212W Piston Rod Assembly wO Ring 1124 14 20 x 12 RH Machine Screw4
1232MS M23A 10 Lockwasher SS 2
1213W Piston Rod Seal Assembly Pre692
Incl 1213A B C D PHC PARTS
1213A U Cup Seal Pre692 Part No Delrin Washer Pre692 1226A
Housing Screw 1420 x 1 14 SS 4
1213C Snap Ring Pre692 1226C Plastic Spacer Washer 4
1213D White Neoprene Washer Pre692 1301PW Toilet Base Assembly 1301P 1343
1214W Piston Shaft Seal Cartridge Assy 1214 F081 Bowl Bolt 14 20 x 2 SS Hex head
1214A 1214B Fits pumps mfg after 692 RARITAN INSTALLATION Clevis Pin 3 Part No Discharge
Valve Cap 163000 InLine Strainer
1218 Fulcrum Link 2 1PCP22 CP Cleans Potties 22 oz
1222AW 90 Discharge wFlange Std CDS Continuous Duty Straight Discharge Opt CH104
Rectifier Box w switch for PHEII DC120
1223B Flange Nut 3816 SS 2 CHDPS120 Double Pole Switch for CH115V
1226 Housing Screw 1420 x 1 SS 4 CHT Permanent Compact Holding Tank
1226B Nut 1420 SS 8 CON22 Concentrate 22 oz bottle
1228CW Flapper Valve Assembly 12 Holes PBS Push Button Switch
1232MS Piston O Ring PHT Portable Compact Holding Tank
1234 Bowl Gasket SH Sanitation Hose sold by the foot
1236C Bowl Elbow SL Super Lube 12 oz tube
1246W Base Cover 2 pcs TWK Toilet Water Marine Head Disinfectant Kit
1248W Base wPlug VL 34 Vented Loop 34
1249 Base Plug VL 1 12 Vented Loop 1 12
1250W Base and Cover Assy1246W and1248W YV Y Valve
C253 Joker Valve
CH42 Hose ID BOWL SEAT
CH43P Hose Clamp 2 Part No 14 20 x 516 SS Socket Set Screw 1236AW Spud assy
F081 Bowl Bolt 1420 x 2 SS Hex head 1237W Marinesize Bowl assy
LWS Intake and Discharge Valve Spring 2 1244W White Bowl assy
RNI Nylon Shoulder Washer 1238A Marinesize seat cover
1245 seat cover
PARTS FOR ELECTRIC DRIVE 1PCP22 Clean Potties 22 oz
Part No Part Name VCAP Vinyl Cap
1100W Gear Box Housing Assembly
1102 Worm OVERHAUL KITS
1104 Ball Bearing Part No Snap Ring PHRKII Seal
Rubber Connection wSleeve PHRKIIC Seal mfgafter 692
Specify Voltage
EXPLODED PARTS VIEWS PHII MARINE TOILET AND PHECKII ELECTRIC
CONVERSION UNIT
1206W 1236C
1218 1210A CH43P
1210A
1124 1210
1218
1209BW
1216
1204B
1216
1202 F005 1217
1203B1 1223B
1211PL 1202
1203B3
1214
1222AW
1203BW 1214A LWS CH42
1203B 1214B 1201 1222B
1203B2
C253
1201 1213W Seal
1226 Assy on Units
1226B Built Before
June 1992
RNI 1203W
1234 1213D
1200CW 1213C
1213A 1213B
1115
1249 1212W
Assy
1228CW
1232MS
F081
1248W 1109
1226B
1106S
1246W 1106A
1105 1106W
1100W
1104
1124
1102
1113
1226A
1123
1115
1122
1226C 1120 M23A
1108A 1115A
1113
1110
F081 1100
1111
1118
1115A
1301PW 11191119A 1112
PHC Toilet Base Assembly
PHC Base does not allow the PHC to be converted to a PHEII 1116BW 1117B
LIMITED WARRANTY
Raritan Engineering Company warrants to the original purchaser that this product is free of defects in materials
or workmanship for a period of one year from the products date of purchase Should this product prove defective
by reason of improper workmanship andor materials within the warranty period Raritan shall at its sole option
repair or replace the product
1 TO OBTAIN WARRANTY SERVICE Consumer must deliver the product prepaid together with a detailed
description of the problem to Raritan at 530 Orange St Millville NJ 08332 or 3101 SW 2nd Ave Ft
Lauderdale FL 33315 When requesting warranty service purchaser must present a sales slip or other document
which establishes proof of purchase THE RETURN OF THE OWNER REGISTRATION CARD IS NOT A
CONDITION PRECEDENT OF WARRANTY COVERAGE However please complete and return the owner
Registration Card so that Raritan can contact you should a question of safety arise which could affect you
2 THIS WARRANTY DOES NOT COVER defects caused by alterations repairs or service of this
product by anyone other than Raritan defects in materials or workmanship supplied by others in the process of
installation of this product defects caused by installation of this product other than in accordance with the
recommended installation instructions or standard industry procedures physical abuse to or
misuse of this product This warranty also does not cover damages to equipment caused by fire flood external
water excessive corrosion or Act of God
3 ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND ANY REMEDY FOR BREACH OF
CONTRACT WHICH BUT FOR THIS PROVISION MIGHT ARISE BY IMPLICATION OR OPERATION OF
LAW IS HEREBY EXCLUDED AND DISCLAIMED ALL IMPLIED WARRANTIES SUCH AS THOSE OF
AND OF FITNESS FOR A PARTICULAR PURPOSE IF APPLICABLE AS WELL
AS ANY IMPLIED WARRANTIES WHICH MIGHT ARISE BY IMPLICATION OF LAW ARE EX
PRESSLY LIMITED TO A TERM OF ONE YEAR SOME STATES DO NOT ALLOW LIMITATIONS ON
HOW LONG A LIMITED WARRANTY LASTS SO THE ABOVE LIMITATION MAY NOT APPLY TO
4 UNDER NO CIRCUMSTANCES SHALL RARITAN BE LIABLE TO PURCHASER OR ANY OTHER
PERSONS FOR ANY SPECIAL OR CONSEQUENTIAL DAMAGES WHETHER ARISING OUT OF
BREACH OF WARRANTY BREACH OF CONTRACT OR OTHERWISE SOME STATES DO NOT
ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES SO
THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU
5 No other person or entity is authorized to make any express warranty promise or affirmation of fact or to assume
any other liability on behalf of Raritan in connection with its products except as specifically set forth in this
warranty
6 This warranty gives you specific legal rights and you may also have other rights which vary from state to state
530 Orange Street PO Box 1157 Millville NJ 08332 USA
Telephone 8568254900 FAX 8568254409
Southern Office and Plant
3101 SW Second Avenue Fort Lauderdale FL 33315 USA
Telephone 9545250378 FAX 0701wmr Subject to Change Without Notice Printed in USA

Ad by Google

Disclaimer:
The information on this web site has not been checked for accuracy. It is for entertainment purposes only and should be independently verified before using for any other reason. There are five sources. 1) Documents and manuals from a variety of sources. These have not been checked for accuracy and in many cases have not even been read by anyone associated with L-36.com. I have no idea of they are useful or accurate, I leave that to the reader. 2) Articles others have written and submitted. If you have questions on these, please contact the author. 3) Articles that represent my personal opinions. These are intended to promote thought and for entertainment. These are not intended to be fact, they are my opinions. 4) Small programs that generate result presented on a web page. Like any computer program, these may and in some cases do have errors. Almost all of these also make simplifying assumptions so they are not totally accurate even if there are no errors. Please verify all results. 5) Weather information is from numerious of sources and is presented automatically. It is not checked for accuracy either by anyone at L-36.com or by the source which is typically the US Government. See the NOAA web site for their disclaimer. Finally, tide and current data on this site is from 2007 and 2008 data bases, which may contain even older data. Changes in harbors due to building or dredging change tides and currents and for that reason many of the locations presented are no longer supported by newer data bases. For example, there is very little tidal current data in newer data bases so current data is likely wrong to some extent. This data is NOT FOR NAVIGATION. See the XTide disclaimer for details. In addition, tide and current are influenced by storms, river flow, and other factors beyond the ability of any predictive program.